Appendix D – Troubleshooting
If you are having trouble with your Modbus Card, please consult the following resources in this order:
1. Consult the following list of common problems to see if one matches yours.
2. Consult the support section of our website at
http://www.profireenergy.com.
3. Contact us on our support line at 1-855-PRO-FIRE (776-3473).
Menu 6 Does Not Exist on my PF2100
The firmware version is too old and does not support expansion cards.
Verify that the firmware version in your PF2100 is old using the procedure on page 3.
Install the card in a different system with the correct firmware version.
Contact Profire to arrange for a firmware update.
The “Run” LED is Not Blinking
The Modbus Card is not getting power from the Terminal Card or is damaged.
Double check that the Modbus Card is installed properly on the Terminal
Card and that no pins are bent or damaged.
Using a multimeter, probe pins 4 and 6 on header P1 as illustrated in
Figure 14 to verify that 3.5V is present.
Contact Profire to arrange for a hardware repair or replacement.
The “RX” LED Does Not Light When the Master Sends a Command
The Modbus Card is not enabled, the wiring is incorrect, the baud rate is incorrect,
or the card is damaged.
Double check that the Modbus Card is enabled in the menu 6.8.
Double check the wiring of the card and the master device
Double check the baud rate settings for the card and the master device
Contact Profire to arrange for a hardware repair or replacement.